Motor Protection Relay JRC 113

We are offering a quality approved assortment of Motor Protection Relays. The Motor Protection Relays we offer is recommended by the clients for their availability in various sizes and specifications.

FOB Price:
Get Latest Price
Minimum Order Quantity:
Not mentioned
Payment Terms:
Cash,Cheque,Demand Draft
Business Type:
Manufacturer, Distributor / Wholesaler
Request for Quote
Product manufactured In:
India
Type :
Motor Protection Relay
Model :
JRC 113
Weight :
2500 gms. (approx)
Accuracy test :
IEC 60255-3
Insulation test :
IEC 60255-5
Case Size Fascia :
144sq mm, depth 232mm
Installation :
Flush Mounting
Panel Cutout :
138mm x 138mm
Current rating ( In ) :
1A / 5A
TRIP / ALARM Rating :
10A at 24V DC/230V AC
Loaded contact :
10,000 operations min
Unloaded contact :
100,000 operations min
Current setting ranges :
O/c 50 to 200% in steps of 10%
Locked rotor current :
50 to 800% of rated current in steps of 50%
Block on Start time setting range (T1) :
5 to 35 seconds in steps of 2 sec.
O/C withstand time setting range (T2) :
1 to 16 seconds in steps of 1 sec
Locked rotor withstand time setting range (T3) :
0.5 to 4 seconds in steps of 0.25 sec.
Additional Details

Principle of Operation:

This is a Microprocessor based relay which has been designed to sense the load currents in all the three phases of an AC motor. It monitors the levels of these currents continuously, giving output signals for relay and LED driver circuits.

 

Features:

Software based design

‘Block on Start’ feature provides very accurate overload protection

Definite time over load protection

Locked rotor current protection

Single phasing protection

Wide setting ranges

Draw -out case

 

Application:

The relay provides Over load protection of AC motors driving conveyors, crushers, machine tools, compressors, fans etc.

 

Aux. Supply :

1) 20 to 60V DC

2) 75 to 150V AC / DC

3) 175 to 300V DC

    185 to 250V AC

 

Insulation:

2KV RMS, 50 Hz for 1 minute / 2.5 KV for 1 sec . Between all terminals and earth. 

1 KV RMS, 50 Hz for 1 minute across open contacts 

 

Settings:

Current setting ranges :  O/c 50 to 200% in steps of 10% 

Locked rotor current : 50 to 800% of rated current in steps of 50%

Block on Start time setting range (T1) : 5 to 35 seconds in steps of 2 sec.

O/C withstand time setting range (T2) : 1 to 16 seconds in steps of 1 sec.

Locked rotor withstand time setting range (T3) : 0.5 to 4 seconds in steps of 0.25 sec.

 

Burden:

current input :

0.2VA Per phase (at Rated 5A)

0.05VA per Phase (at Rated 1A)

Aux. supply :

Less than 8W ( Non operated) 

Less than 10W (Operated)

With almost more than a decade of experience and rich technological expertise, we are able to offer a precision designed range of Electrical Protection Instruments.

More details:View company website

Buyers feedback
Have you used this product?
Be the first to review now.

Email to this Supplier

*Name :
*Email :
*Country :
*Mobile :
To :
Aaryaa M S(Managing Director)
*Description :
 

You might also be interested in

Online UPS

Min Order Qty :
NA
Add to Cart

Furnace Transformers

Min Order Qty :
NA
Add to Cart

iCube DC UPS

Min Order Qty :
1 Pieces
Add to Cart
Get Verified, Sell more with

Its Free

Verify Now

Please Wait!!!
We are processing your request
Note : Do not Refresh or Close the window while we are processing your request

Sign in to continue to Pepagora

Don’t have an Account? Sign Up | Forgot Password?

Create your Pepagora Account
I am a
Can't understand captcha? Change