Neutral Earthing Resistor Monitoring Relay JRV 402

Banking on our extensive industry experience, we have been able to provide the JRV 402 neutral grounding resistance relay. These relays have solid-state circuits, voltage sensing and have a low energy consumption.

FOB Price:
Get Latest Price
Minimum Order Quantity:
Not mentioned
Payment Terms:
Cash,Cheque,Demand Draft
Business Type:
Manufacturer, Distributor / Wholesaler
Request for Quote
Product manufactured In:
India
Product :
Neutral Earthing Resistor Monitoring Relay
Output Contacts :
10A At 24V DC / 230V AC
Auxiliary Supply :
230V, Plus-Minus 10%, 50Hz
Relay :
Two Changeover
Relay Ratings :
5A At 24V DC/230V AC, 50Hz.
Working Voltage 565V, 3, 50Hz, With Neutral Resistance Of 435 Ohms :
565V, 3, 50Hz, With Neutral Resistance Of435 Ohms.
Tripping Level :
Resistance More Than 150% Of 435 Ohms
Insulation :
Between All Terminals And Cases
Relay :
Voltage Relay
Unloaded Contact :
1,000,000 Operations.
Loaded Contact :
100,000 Operations
Source :
Electrical
Relay Type :
JRV 402
Panel Cutout :
73mm X 138mm
Weight :
1000gms. (Approx)
Price :
Negotiable
Installation :
Flush Mounting
Case Size Fascia :
83 X 148sq Mm, Depth 104mm
Burden Auxiliary Supply :
Less Than 5VA
Additional Details

Very low DC current flows through the NER and is monitored in the relay. If there is an open circuit in the resistor or a considerable change in the value of the resistor, this is detected in the monitoring circuit. After detecting the change, the timer is short-circuited and the output relay is de-energized at the end of the internal delay (5 sec.). The relay contact can be externally connected to the alarm/trip circuit as required. Normally, the output relay is energized. If there is a fault in Aux. Provide the output relays and extend the alarm/trip signal.

 

Features:

Solid state reliability

Integrated test facility

High sensitivity

Low charge

 

Insulation:

2KV RMS, 50 Hz for 1 minute / 2.5 KV for 1 sec Between all terminals and cases.

1KV RMS, 50 Hz for 1 minute across open contacts

 

Application:

The relay is used to monitor the neutral grounding resistance. The neutral of the transformer is grounded through a resistor. This resistor is called the neutral grounding resistor (NER). Neutral grounding resistors are used to limit the fault current across the transformer during ground fault conditions. The health of TNS is important because open resistance would make ground leakage protection operational and dangerous.

With almost more than a decade of experience and rich technological expertise, we are able to offer a precision designed range of Electrical Protection Instruments.

More details:View company website

Buyers feedback
Have you used this product?
Be the first to review now.

Email to this Supplier

*Name :
*Email :
*Country :
*Mobile :
To :
Aaryaa M S(Managing Director)
*Description :
 

You might also be interested in

Get Verified, Sell more with

Its Free

Verify Now

Please Wait!!!
We are processing your request
Note : Do not Refresh or Close the window while we are processing your request

Sign in to continue to Pepagora

Don’t have an Account? Sign Up | Forgot Password?

Create your Pepagora Account
I am a
Can't understand captcha? Change